i-Vu® CCN Router
CIV-CR
Network & Integration Device
Network device used to connect Ethernet-based Local Area Network (LAN) to the Carrier Comfort Network® (CCN).
The i-Vu CCN Router provides scalability for larger Carrier systems. It connects an Ethernet-based Local Area Network (LAN) to the Carrier Comfort Network (CCN™). Because the i-Vu CCN Router allows for the use of existing LAN wiring, it is an ideal solution for integrating CCN into any building or facility. The i-Vu CCN Router has one EIA-485 port for connecting to the CCN bus, and one 10/100 Base-T Ethernet port for connecting to the building LAN. Each i-Vu CCN Router can connect to up to 140 CCN devices. The i-Vu CCN Router also stores trend data and time schedules for the CCN devices that are connected to it.


Functions
The i-Vu CCN Router functions in one of the following modes, depending on configuration:
- Gateway - Provides access to the CCN bus from an i-Vu web server that resides on the Ethernet. The Router is serving as the access node from the Ethernet to the CCN and is responsible for maintaining a routing table of CCN system elements.
- Bridge - Acts as a CCN/Ethernet interface device in applications where the Ethernet is being used to connect separate CCN buses. This application requires an additional Router functioning as a Gateway.
Communication Ports | Port E1:10/100 BaseT Ethernet port for LAN and BACnet IP communications
Port S1 (CCN): EIA-485 port for CCN Network and/or CCN Service Tool connection (9600 bps & 38.4 kbps) |
Protection | Incoming power and network connections are protected by non-replaceable internal solidstate polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events. |
Real Time Clock | Battery-backed real time clock |
Battery | 10-year Lithium CR123A battery provides a maximum of 720 hours of time retention during power outages. To conserve battery life, battery backup turns off after a specified number of days defined in the module driver. |
Status Indicators | LED status indicators for BACnet MS/TP communication, Ethernet port communication, and low battery status. 7-segment status display for running, error and power status. |
Controller Addressing | Rotary DIP switches set address of Router. |
Listed By | UL-916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15-Subpart B-Class A |
Environmental Operating Range | Operating: 0° to 140°F (-18° to 60°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing |
Power Requirements | 24VAC +/- 10%, 50-60Hz
24VA power consumption 26VDC (25V min, 30V max) Single Class 2 source only, 100VA or less |
Physical | Rugged aluminum cover and removable screw terminal blocks. |
Functions
The i-Vu CCN Router functions in one of the following modes, depending on configuration:
- Gateway - Provides access to the CCN bus from an i-Vu web server that resides on the Ethernet. The Router is serving as the access node from the Ethernet to the CCN and is responsible for maintaining a routing table of CCN system elements.
- Bridge - Acts as a CCN/Ethernet interface device in applications where the Ethernet is being used to connect separate CCN buses. This application requires an additional Router functioning as a Gateway.
Communication Ports | Port E1:10/100 BaseT Ethernet port for LAN and BACnet IP communications
Port S1 (CCN): EIA-485 port for CCN Network and/or CCN Service Tool connection (9600 bps & 38.4 kbps) |
Protection | Incoming power and network connections are protected by non-replaceable internal solidstate polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events. |
Real Time Clock | Battery-backed real time clock |
Battery | 10-year Lithium CR123A battery provides a maximum of 720 hours of time retention during power outages. To conserve battery life, battery backup turns off after a specified number of days defined in the module driver. |
Status Indicators | LED status indicators for BACnet MS/TP communication, Ethernet port communication, and low battery status. 7-segment status display for running, error and power status. |
Controller Addressing | Rotary DIP switches set address of Router. |
Listed By | UL-916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15-Subpart B-Class A |
Environmental Operating Range | Operating: 0° to 140°F (-18° to 60°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing |
Power Requirements | 24VAC +/- 10%, 50-60Hz
24VA power consumption 26VDC (25V min, 30V max) Single Class 2 source only, 100VA or less |
Physical | Rugged aluminum cover and removable screw terminal blocks. |