Skip to main content

24/7 Commercial Service

call 1-800-379-6484

Find an expert

WeatherExpert® Light Commercial Packaged High Outdoor Air System
50WE

Cooling Only or Electric Cooling/Heating Units with Puron Advance ™

6 to 15 Nominal Tons

Carrier’s 50WE WeatherExpert® rooftops (RTU) with Puron Advance™ (R-454B) and EcoBlue™ Fan Technology, offer an environmentally sustainable solution for a brighter future. With a GWP of 466 and similar performance to R-410A, Puron Advance easily exceeds the EPA's new, stringent, <700 GWP refrigerant requirement. Our direct drive EcoBlue™ indoor fan system uses a Vane Axial fan and electronically commutated motor and all 50WE models are designed and configured for expanded envelope operation. 50WE models can operate as a single zone AC, multizone VAV unit, or with up to 100% outdoor air for ventilation or make-up air. All units include new options that enable 100% outdoor air operation including modulating low load protection valve to prevent refrigerant circuit issues, and double wall construction option. All units include Carrier SmartVu™ controls for control flexibility, ease of setup and commissioning, and simplified troubleshooting.


puron-advance-logo

Performance Features

  • Puron Advance (R-454B) refrigerant meets and exceeds EPA’s new Low GWP requirements 
  • New – UL 60335-2-40 Certified A2L leak detection and dissipation system factory installed standard 
  • Direct Drive EcoBlue™ Technology indoor fan system uses Vane Axial fan design & electronically commutated motor 
  • Three-stage cooling capacity control on all models 
  • Large face area hot gas reheat (HGRH) coil with modulating control valve for dehumidification operation 
  • New Unit Control Board with intuitive quick fan speed adjustment 
  • IEER’s up to 20.5, EER’s up to 13.1 
  • Cooling operating range up to 125 °F (52°C) and down to 40°F (4°C) using winter start kit 
  • Innovative corrosive-resistant composite condensate pan in accordance with ASHRAE 62 Standard, sloping design; side or center drain 
  • Pre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection 
  • Carrier SmartVu controls with 7” touchscreen display 
  • Single zone, multi-zone, 100% outdoor air, or multistage heat/cool thermostat operating modes 
  • Units meet ASHRAE 90.1 energy efficiency levels.

Maintenance Features

  • Condensate overflow switch 
  • Hinged access panels with easy grip handles 
  • Innovative, easy starting, no-strip screw feature on unit access panels 
  • Two-inch disposable return air filters 
  • Tool-less filter access door 
  • New Vane Axial evaporator-fan system has no fan belts, pullies, blower shaft and blower bearings with slide out design

Installation Features

  • All units ship vertical and are easily field convertible from vertical to horizontal airflow. 08-12 models require an accessory supply duct cover. 
  • Provisions for thru-the-bottom power entry capability as standard 
  • Single point gas and electric connections 
  • Full perimeter base rail with built-in rigging adapters and fork truck slots

Reliability Features

  • A2L leak detection and dissipation system standard 
  • SmartVu™ controls with system monitoring and alarming 
  • Proven tandem scroll compressor design with internal line-overload protection 
  • 24-volt control circuit protected with resettable circuit breaker 
  • Direct drive supply fan 
  • Totally enclosed condenser motors with permanently lubricated bearings 
  • Low and high refrigerant pressure sensors 
  • Solid-state electronic direct spark ignition system 
  • Flame roll-out safety protector 
  • Liquid line filter drier 
  • Cooling and dehumidification lockouts based on outdoor air or entering coil air temperatures

Standard Limited Warranty

  • 5-year electric heater element
  • 5-year compressor parts 
  • 3-year parts SmartVu™ Controller 
  • 1-year parts 
  • Additional extended warranty packages available

Factory-Installed Options

  • Medium or high electric heaters with SCR control
  • Return air CO2 sensor 
  • Return and/or supply air smoke detector 
  • High static supply fan motor 
  • Variable speed supply fan control based on duct static or space static pressure 
  • Corrosion resistant options for evaporator and condenser coils 
  • Ultra-low leak Integrated economizer system 
  • Powered or un-powered convenience outlet 
  • 4” filter track with 4” MERV 13 filters 
  • Non fused disconnect switch or HACR circuit breaker 
  • Double wall construction 
  • Knockdown roof curbs 
  • Field installed economizers 
  • Space temperature, humidity, and CO2 sensors 
  • Thermostats

Cooling Only or Electric Cooling/Heating Models (50WE)

Nominal Cooling Ton Size Cooling Stages AHRI Efficiency IEER Dimensions (in) LxWxH Electric Heat Range (kW) Approx Unit Weight (lbs)
6 3 20.5 88x59x49 10.4-25.0 999
7.5 3 20.5 116x63x57 16.0-36.0 1453
10 3 20.2 116x53x57 16.0-50.0 1506
15 2 18.8 141x86x57 24.8-50.0 2016


AHRI = Air-Conditioning, Heating & Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
IEER = Integrated Energy Efficiency Ratio

NOTES
1. Rated and certified under ARI Standard 340/360
2. Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor air temp and 95°F (35°C) db outdoor air temp.
3. 50WE units generally comply with ASHRAE 90.1-2010 Energy Standard. Please review size specific data for compliance.
4. 50WE units comply with US Energy Policy Act (2005).

Performance Features

  • Puron Advance (R-454B) refrigerant meets and exceeds EPA’s new Low GWP requirements 
  • New – UL 60335-2-40 Certified A2L leak detection and dissipation system factory installed standard 
  • Direct Drive EcoBlue™ Technology indoor fan system uses Vane Axial fan design & electronically commutated motor 
  • Three-stage cooling capacity control on all models 
  • Large face area hot gas reheat (HGRH) coil with modulating control valve for dehumidification operation 
  • New Unit Control Board with intuitive quick fan speed adjustment 
  • IEER’s up to 20.5, EER’s up to 13.1 
  • Cooling operating range up to 125 °F (52°C) and down to 40°F (4°C) using winter start kit 
  • Innovative corrosive-resistant composite condensate pan in accordance with ASHRAE 62 Standard, sloping design; side or center drain 
  • Pre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection 
  • Carrier SmartVu controls with 7” touchscreen display 
  • Single zone, multi-zone, 100% outdoor air, or multistage heat/cool thermostat operating modes 
  • Units meet ASHRAE 90.1 energy efficiency levels.

Maintenance Features

  • Condensate overflow switch 
  • Hinged access panels with easy grip handles 
  • Innovative, easy starting, no-strip screw feature on unit access panels 
  • Two-inch disposable return air filters 
  • Tool-less filter access door 
  • New Vane Axial evaporator-fan system has no fan belts, pullies, blower shaft and blower bearings with slide out design

Installation Features

  • All units ship vertical and are easily field convertible from vertical to horizontal airflow. 08-12 models require an accessory supply duct cover. 
  • Provisions for thru-the-bottom power entry capability as standard 
  • Single point gas and electric connections 
  • Full perimeter base rail with built-in rigging adapters and fork truck slots

Reliability Features

  • A2L leak detection and dissipation system standard 
  • SmartVu™ controls with system monitoring and alarming 
  • Proven tandem scroll compressor design with internal line-overload protection 
  • 24-volt control circuit protected with resettable circuit breaker 
  • Direct drive supply fan 
  • Totally enclosed condenser motors with permanently lubricated bearings 
  • Low and high refrigerant pressure sensors 
  • Solid-state electronic direct spark ignition system 
  • Flame roll-out safety protector 
  • Liquid line filter drier 
  • Cooling and dehumidification lockouts based on outdoor air or entering coil air temperatures

Standard Limited Warranty

  • 5-year electric heater element
  • 5-year compressor parts 
  • 3-year parts SmartVu™ Controller 
  • 1-year parts 
  • Additional extended warranty packages available

Factory-Installed Options

  • Medium or high electric heaters with SCR control
  • Return air CO2 sensor 
  • Return and/or supply air smoke detector 
  • High static supply fan motor 
  • Variable speed supply fan control based on duct static or space static pressure 
  • Corrosion resistant options for evaporator and condenser coils 
  • Ultra-low leak Integrated economizer system 
  • Powered or un-powered convenience outlet 
  • 4” filter track with 4” MERV 13 filters 
  • Non fused disconnect switch or HACR circuit breaker 
  • Double wall construction 
  • Knockdown roof curbs 
  • Field installed economizers 
  • Space temperature, humidity, and CO2 sensors 
  • Thermostats

Cooling Only or Electric Cooling/Heating Models (50WE)

Nominal Cooling Ton Size Cooling Stages AHRI Efficiency IEER Dimensions (in) LxWxH Electric Heat Range (kW) Approx Unit Weight (lbs)
6 3 20.5 88x59x49 10.4-25.0 999
7.5 3 20.5 116x63x57 16.0-36.0 1453
10 3 20.2 116x53x57 16.0-50.0 1506
15 2 18.8 141x86x57 24.8-50.0 2016


AHRI = Air-Conditioning, Heating & Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
IEER = Integrated Energy Efficiency Ratio

NOTES
1. Rated and certified under ARI Standard 340/360
2. Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor air temp and 95°F (35°C) db outdoor air temp.
3. 50WE units generally comply with ASHRAE 90.1-2010 Energy Standard. Please review size specific data for compliance.