Gemini® Two-Stage Commercial Split System
Technical Specifications
At a glance
Compressor Type
Cooling OnlyRefrigerant
R-410AType
Condensing UnitCapacity
10 - 20 TonsMatched Air Handler(s)
40RUA, 40RUQ, 40RUSFeatures
Performance Features
38AUD two cooling stages with EERs from 11.0 to 11.2
ASHRAE 90.1 Efficiency Compliant
Standard crankcase heater
Compressor vibration isolation
Low ambient temperature control
Unit performance certified in accordance with ARI standard 340/360
Reliability Features
High and low-pressure switches
Anti-short cycling protection
Prepainted, galvanized steel cabinets that passes 500-hour salt-spray test
Compressor overload protection
Scroll compressor
E-Coat coil protection
UL, UL, Canada or ETL approved
Installation Features
Shipped with Puron (R-410A) refrigerant partial charge
Single-piece design
Perimeter base rail with forklift slots and lifting holes facilitates rigging
Suitable for mounting on the ground or the rooftop
24V control circuit transformer permits quick, easy wiring of thermostats
Maintenance Features
Comfort Alert™ diagnostic board
Powered and non-powered 115-v convenience outlet
Compressor access panel with easy grip handle
Easy starting, no-strip screw feature
Non-fused disconnect switch
Standard Limited Warranty
5 years parts only on compressor
One year parts only on all other parts
Options
Factory-Installed Options
Non-fused Disconnect
Premium, E-coated condenser coil
Convenience outlet (powered)
Low ambient temperature Motormaster® control
Louvered hail guards
Modulating unloading device (sizes 12, 16, and 25)
Field-Installed Accessories
Low ambient temperature Motormaster® control
Louvered hail guard
Programmable thermostats
Physical Data
38AUD/40RUA AHRI Cooling Ratings
| Unit | Cooling Stages | Nominal Capacity (Tons) | Net Cooling Capacity (MBH) | Total Power (kW) | EER | IEER |
| 38AUD12/40RUA12 | 2 | 10 | 117.0 | 10.4 | 10.3 | 11.6 |
| 38AUD14/40RUA14 | 2 | 12.5 | 148.0 | 13.4 | 11.0 | 12.0 |
| 38AUD16/40RUA16 | 2 | 15 | 184.0 | 16.4 | 11.2 | 11.8 |
| 38AUD25/40RUA25 | 2 | 20 | 240.0 | 21.6 | 11.0 | 11.2 |
AHRI = Air-Conditioning, Heating and Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
EER = Energy Efficiency Ratio
IEER = Integrated Energy Efficiency Ratio
COP = Coefficient of Performance
NOTES
- Rated in accordance with ARI Standard 340/360---07, as appropriate.
- Ratings are based on:
- Cooling Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 35°C (95°F) db outdoor air temp.
- IEER Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 4 various outdoor temperatures.
- All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.