WeatherMaster® 50GE Rooftop 3-25 Ton High-Efficiency Electric Heat / Electric Cooling
Technical Specifications
At a glance
Type
Electric Heat / Electric CoolingRefrigerant
R-454BCapacity Range
3 - 25 TonsMulti-Zone VAV is available on select 3-stage configurations from 6-25 tons.
Efficiency (SEER/IEER)
16.8, 17.7Cooling/Application
Multi-Zone VAV (MZVAV)2-stage standard configurations remain available. MZVAV is available only with 3-stage cooling and the factory-integrated TruVu PIC.
Features
Product Features
Multi-Zone VAV application Available on select 3-stage 48GE and 50GE configurations from 6-25 tons. One rooftop unit can serve multiple zones through VAV terminals.
Three-stage capacity control Fixed-speed tandem-scroll architecture provides 40% / 60% / 100% cooling stages to match building load without an inverter-based compressor.
TruVu Product Integrated Control (PIC) Factory-integrated control required for MZVAV-equipped configurations.
Airside Linkage Coordinates the rooftop unit with Carrier TruVu/Open VAV zone controllers by exchanging system and zone information.
Standalone VAV operation Supports operation as a VAV rooftop serving third-party BACnet air terminals when applied and commissioned per product literature.
Building integration Supports BACnet IP and BACnet MS/TP and is native to i-Vu.
Setup and service visibility Equipment Touch startup wizard, alarms, trending, service test functions and suction/discharge pressure inputs support commissioning and troubleshooting.
Supply fan control EcoBlue™ variable-speed supply fan modulates to maintain the configured duct-static-pressure setpoint.
Ventilation and economizer control MZVAV sequence supports economizer, minimum ventilation and demand-controlled ventilation functions when properly configured.
A2L integration Includes R-454B leak-dissipation input/output logic and system interaction
2-stage configurations Available for standard 48GE/50GE applications. MZVAV is not available on 2-stage units.
3-stage MZVAV configurations Available on select 6, 7.5, 8.5, 10, 12.5, 15, 17.5, 20 and 25 ton configurations; final availability is subject to current product-selection data.
Controls SystemVu remains applicable to standard configurations. TruVu PIC is required and factory-integrated on MZVAV-equipped configurations.
Economizer Required/standard for the MZVAV configuration.
Humidi-MiZer Availability varies by configuration and later program phase.
Carrier linked system Supports Carrier TruVu/Open VAV terminals with Airside Linkage.
Third-party system Supports standalone VAV operation with third-party BACnet terminals; application, networking and commissioning requirements.
User interface / commissioning Equipment Touch is the documented setup path in current program requirements.
Performance Features
Puron Advance (R-454B) refrigerant meets and exceeds EPA’s new Low GWP requirements
New – UL 60335-2-40 Certified A2L leak detection and dissipation system factory installed standard
Direct Drive EcoBlue™ Technology indoor fan system uses Vane Axial fan design & electronically commutated motor
Two-stage cooling capacity control on all models or Three-stage from 07-28 models
New Unit Control Board with intuitive quick fan speed adjustment
SEER2 up to 16.8, IEER of 17.7
Cooling operating range up to 125 °F (52°C) and down to 40°F (4°C) using winter start kit
Innovative corrosive-resistant composite condensate pan in accordance with ASHRAE 62 Standard, sloping design; side or center drain
Pre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection
Units meet ASHRAE 90.1 energy efficiency levels.
Maintenance Features
New unit control board facilitating simple safety circuit troubleshooting and simplified control box arrangement as well as easy intuitive fan speed adjustment
Access panels with easy grip handles
Innovative, easy starting, no-strip screw feature on unit access panels
Tool-less filter access door
Optional hinged access panels also available
NEW Direct Drive – EcoBlue™ Technology Indoor fan system uses Vane Axial fan design and electronically commutated motor with beltless design
Two-inch disposable return air filters
Installation Features
Same footprint as prior Carrier models for that original fit; reduces installation costs and time
Field convertible from vertical to horizontal airflow configuration on units up to 15 tons
Provisions for thru-the-bottom power entry capability as standard
Single point gas, electric, and controls connections
Full perimeter base rail with built-in rigging adapters and fork truck slots
Reliability Features
A2L leak detection and dissipation system standard
Scroll compressors with internal line-break overload protection
24-volt control circuit protected with resettable circuit breaker
Permanently lubricated direct-drive ECM evaporator-fan motor
Totally enclosed condenser motors with permanently lubricated bearings
Low pressure and high-pressure switch protection
Standard Limited Warranty
5 years parts only compressor
5 years electric heaters
3 year SystemVu™ controller
One year parts only on all other parts
Additional extended warranty packages available
Options
Factory-Installed Options
Temperature Sensing EconoMi$er with relief
Enthalpy Sensing EconoMi$er with relief
Humidi-MiZer® Adaptive Dehumidification System
Stainless Steel Gas Heat Exchangers
Return Air Smoke Detector
Supply Air Smoke Detector
CO2 Sensor
Condensate Overflow Protection
Multiple Static Fan Capabilities
Phase Monitor/Protection
Thru-The-Base Utility Connections
Louvered Hail Guards
Non-Fused Disconnect Switch
HACR breaker
4" MERV-13 Filters
Low Ambient Controls
Foil Face Insulation
Hinged Access Panels
Unpowered Convenience Outlet
Powered Convenience Outlet
Coated Coils: Pre-Coat, E-Coat, Copper/Copper
Electrical Mechanical Controls
SystemVu™ Integrated Communicating Controls
Extended Warranty Protection Plans
Physical Data
Electric Heat/Electric Cooling & Cooling Only Models (50GE)
| Nominal Cooling Ton Size | Cooling Stages | AHRI Efficiency (SEER2) IEER | Dimensions LxWxH (in) | Electric Heat Nominal kW Range | Approx. Unit Weight (lbs) |
| 3.0 | 2 | (16.8) | 74x47x33 | 4.0 to 16.0 | 490 |
| 4.0 | 2 | (16.8) | 74x47x33 | 4.0 to 21.0 | 510 |
| 5.0 | 2 | (16.8) | 74x47x41 | 6.0 to 24.0 | 555 |
| 6.0 | 2 or 3 | 17.7 (2-stage) 22.1 (3-stage) | 88x59x41 | 6.0 to 25.0 | 714 |
| 7.5 | 2 or 3 | 17.7 (2-stage) 20.9 (3-stage) | 88x59x49 | 10.4 to 42.4 | 830 |
| 8.5 | 2 or 3 | 17.5 (2-stage) 19.4 (3-stage) | 88x59x49 | 10.4 to 42.4 | 830 |
| 10.0 | 2 or 3 | 17.7 (2-stage) 18.9 (3-stage) | 88x59x49 | 15.0 to 50.0 | 971 |
| 12.5 | 2 or 3 | 16.7 (2-stage) 18.8 (3-stage) | 116x63x57 | 15.0 to 50.0 | 1313 |
| 15.0 | 2 or 3 | 16.7 (2-stage) 19.0 (3-stage) | 127x86x49 | 25.0 to 75.0 | 1644 |
| 17.5 | 2 or 3 | 16.5 (2-stage) 19.2 (3-stage) | 141x86x49 | 25.0 to 75.0 | 1880 |
| 20.0 | 2 or 3 | 17.0 (2-stage) 17.5 (3-stage) | 141x86x57 | 25.0 to 75.0 | 2203 |
| 25.0 | 2 or 3 | 15.2 (2-stage) 18.3 (3-stage) | 157x86x57 | 25.0 to 75.0 | 2296 |
MZVAV Eligibility: Select 3-stage 50GE configurations, 6-25 tons, with factory-integrated TruVu PIC. MZVAV is not available on the 2-stage configurations shown in this table.
AHRI = Air-Conditioning, Heating & Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
IEER = Integrated Energy Efficiency Ratio
SEER2 = Seasonal Energy Efficiency Ratio 2
NOTES
- Rated and certified under ARI Standard 210/240 3-5 ton or 340/360 6+ ton, as appropriate
- Ratings are based on:
- Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor air temp and 95°F (35°C) db outdoor air temp.
- 50GE units generally comply with ASHRAE 90.1-2016 Energy Standard. Please review size specific data for compliance.
- 50GE units comply with US Energy Policy Act (2005).
Documents
Accessory and Kit Data
CRTRVUKT002A00 TruVu Controller Kit for Rooftop Units 48/50FE*20-30, 50FEQ17-28, 48/50GE*17-28, 50GEQ17-28, 48/50FC*20-30, 50FCQ17-28, 48/50GC*17-28, and 50GCQ17-28, 15 to 27.5 Tons
Vertical Power Exhaust Accessory for Gas Heating/Electric Cooling, Electric Cooling, and Heat Pump Rooftop Units, 3 to 15 Tons, CRPWREXH021A01, CRPWREXH022A01, CRPWREXH023A01, CRPWREXH030A01, CRPWREXH080A00, CRPWREXH081A00
Electric Heater and Single Point Box Accessory for Electric Cooling Select 6 to 15 Tons, P/N CRHEATER410A-428A, 451A-453A, CRSINGLE 042A00-045A00, 47A00, 049A00-053A00, 064A00-073A00
CRTRVUKT001A00 TruVu Controller Kit for Rooftop Units 48/50FE*04-16, 50FEQ04-14, 48/50GE*04-14, 50GEQ04-12, 48/50FC*04-16, 50FCQ04-14, 48/50GC*04-14 and 50GCQ04-12, 3 to 15 Tons
CRPWREXH068A00 CRPWREXH069A00 CRPWREXH070A00 Power Exhaust Accessory Single Package Rooftop Units 12.5 to 27.5 Tons
Electric Heater and Single Point Box Accessory for Electric Cooling Small Rooftop Units, Select 3 to 6 Tons CRHEATER323A00-341A00, CRSINGLE037A00-041A00,060A00-063A00
Heater Accessory for Single Package Rooftop Units Select 17.5 to 27.5 Tons P/N CRHEATER454A00-CRHEATER471A00
Brochure
Commercial HVAC Rebates for Unitary & Applied Systems
Untitled Document
Carrier Light Commercial K-12 Vertical - Rooftop Systems
Commercial HVAC Rebates End User Brochure – Unitary & Applied Systems
3-Stage 48/50GE Sell w/MZVAV Sheet
Controls
SystemVu™ Controller Networking Guide
Guide Specifications
50GE Guide Specifications, 3-Stage — 6 to 12.5 Nominal Tons
50GE Guide Specifications, 3-Stage — 15 to 25 Nominal Tons
50GE Guide Specifications, 6 to 12.5 Nominal Tons
50GE Guide Specifications, 15 to 25 Nominal Tons
50GE Guide Specifications, 3 to 5 Nominal Tons
Installation
50GE-*14 WeatherMaster® Single Package Rooftop Cooling Only with Puron Advance™ (R-454B) Refrigerant
WeatherMaster® 50GE 15 to 25 ton, Medium Eff., 2 and 3 Stage, Cooling Only
50GE 07-12 WeatherMaster® Single Package Rooftop Cooling Only with Puron Advance™ (R-454B) Refrigerant
WeatherMaster 50GE 3 to 5 tons, High Eff., Electric Cooling Rooftop Unit
Operation
48/50FE 04-30, 48/50GE 04-28 Single Package Rooftop Units with SystemVu™ Controls Version 2.X and Puron Advance™ (R-454B) Refrigerant, Controls, Start-Up, Operation and Troubleshooting
Product Data
48/50GE**17-28 WeatherMaster® Single-Package Gas Heating/Electric Cooling and Electric Cooling Rooftop Units with Optional Electric Heat with Puron Advance™ Refrigerant (R-454B), 15 to 25 Nominal Tons
48/50GE**17-28 WeatherMaster® 3-Stage Single-Package Gas Heating/Electric Cooling and Electric Cooling Rooftop Units with Optional Electric Heat with Puron Advance™ Refrigerant (R-454B) and EcoBlue Technology, 15 to 25 Nominal Tons
48/50GE04-06 WeatherMaster® Single-Package Gas Heating/Electric Cooling and Electric Cooling Rooftop Units with Optional Electric Heat with Puron Advance™ Refrigerant (R-454B), 3 to 5 Nominal Tons
48/50GE**07-14 WeatherMaster 3-Stage Single-Package Gas Heating/Electric Cooling or Electric Cooling Rooftop Units with Optional Electric Heat with Puron Advance™ Refrigerant (R-454B) and EcoBlue™ Technology, 6 to 12.5 Nominal Tons
48/50GE**07-14 WeatherMaster® Single-Package Gas Heating/Electric Cooling and Electric Cooling Rooftop Units with Optional Electric Heat with Puron Advance™ Refrigerant (R-454B), 6 to 12.5 Nominal Tons
REVIT and 3D DRW Files
50GE Electric, 25T REVIT Files
50GE Electric, 10T REVIT Files
50GE Electric, 3-5T REVIT Files
50GE Electric, 6-8.5T REVIT Files
50GE Electric, 17.5-20T REVIT Files
50GE Electric, 12.5T REVIT Files
50GE Electric, 15T REVIT Files
Service
WeatherMaster 50GE 6 to 12.5 Tons, 2 stage, High Eff. Electric Cooling Rooftop Unit
WeatherMaster 50GE 15 to 25, 2 stage, High Eff., Electric Cooling Rooftop Unit
WeatherMaster 50GE 6 to 12.5 ton, 3 Stage, High Eff., Electric Cooling Rooftop Unit
WeatherMaster 50GE 15 to 25 ton, 3 Stage, High Eff., Electric Cooling Rooftop Unit
WeatherMaster 50GE 3 to 5 tons, High Eff., Electric Cooling Rooftop Unit
Warranty Card
Limited Warranty for Light Commercial Equipment