i-Vu® VAV Zone II Secondary Terminal
Technical Specifications
Features
Application Features
Dual Duct - Hot Deck/Cold Deck control
DOAS applications
Quick and easy test & balancing process
System Benefits
Fully plug-and-play with the Carrier i-Vu Building Automation System
Connects directly to the ACTnet bus on Carrier ZoneCtrl II programmable zone controller
Hardware Features
Separate brushless actuator for reliability and longevity
ACTnet communications bus
Precision differential pressure sensor
Specifications
| Communication Ports | ACTnet Port: For connecting the actuator cable and to the ZoneCtrl II |
| Separable Actuator | Brushless DC motor, torque 45 inch-pounds (5Nm), runtime 205 seconds for 90 degree travel during control. |
| Integral Pressure Sensor | Precision low flow AWM series O-2 in H2O, sensitive down to +/-0.001 in. H2O. Barbed tapered airflow connections accept 3/16 in. (4.75 mm) ID tubing. Allows for readings across the 0-2 in H2O range, accurate to +/-5% of full flow at 2 in. H2O. |
| Protection | Incoming power and network connections are protected by non-replaceable internal solid state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input and output connections are also protected against voltage transient and surge events. |
| Status Indicators | LED status indicators for run status, error, power and motor direction |
| Listed By | UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE EN50082-1997, Fire-retardant plastic ABS, UL94-5VA |
| Environmental Operating Range | Operating: 32° to 130°F (0° to 54°C) 10 to 90% RH, non-condensing Storage: 24° to 140°F (-30° to 60°C) 10 to 90% RH, non-condensing |
| Power Requirements | 24VAC +/- 10%, 50-60Hz, 14 VA power consumption, 26VDC (25V min, 30V max), single class 2 source only, 100 VA or less |
Documents
Installation
Zone Ctrl II and VAV Zone II Secondary Duct Installation and Startup Guide
Product Data
i-Vu Open VAV Zone II Secondary Terminal