AXIS™ 35J Single-Duct Retrofit Terminal
Technical Specifications
At a glance
Type
Single-DuctAirflow Range
45 - 3,700 CFMFeatures
Performance Features
Airflow capacities from 45 to 3700 cfm
Round inlet sizes from 4 in. through 16 in. diameter
Rectangular inlet on size 22
22 gauge, galvanized steel casing construction
Converts high-pressure mechanical constant volume systems to low-pressure variable volume systems
Linear, multiple-point, averaging velocity sensor with an amplified signal
Damper blade has a flexible gasket for tight airflow shutoff
Damper blade operates over a full 90°
All damper assemblies utilize a solid ½ in. shaft that rotates in self-lubricating Delrin® bearings
Pressure independent or dependent controls, including Carrier i-Vu Open (BACnet), Carrier Comfort Network® (CCN), analog, or pneumatic controls
Reliability Features
Casings meet UL-181 and NFPA-90A requirements
Maintenance Features
NEMA 2 steel control enclosure for electric or electronic components
Label information adhered to each unit includes model, size, airflow (cfm), balancing chart, and tagging data
Installation Features
Factory-installed controls
All round collars accommodate standard spiral and flex duct sizes
Balancing taps provided for easy airflow verification
Standard Warranty
One-year parts
Options
Factory-Installed Options
Control options: Analog electronic controls, Carrier i-Vu Open VAV or VVT controls, Carrier Comfort Network (CCN) VAV or VVT controls, Pneumatic controls, No controls or field-supplied DDC (direct digital controls) third party controls for factory mounting
Left-hand or right-hand control enclosure
20 gauge, galvanized steel casing
304 stainless steel casing
Field-Installed Accessories
Remote wall sensor
Supply-air temperature sensor
Documents
Application
35E/J-P-1106: Single Duct Pneumatic Control Sequence 1106: RANO, Multi-Function Control of VAV with or without Optional Reheat
35E/J-A-2101: Single Duct Analog Control Sequence 2101: Cooling Control
35E/J-V-8230: VVT Bypass Damper Control, Carrier Control Package No. 8230
35E/J-P-1107: Single Duct Pneumatic Control Sequence 1107: RANC, Multi-Function Control of VAV with or without Optional Reheat
35E/J-C-4145: ComfortID Zone Pressure Control Variable Air Volume Cooling Control Package No. 4145
35E/J-B-8260: BACnet VVT Damper Control Pressure Dependent Carrier Control Package No. 8260
35E/J-P-1103: Single Duct Pneumatic Control Sequence 1103: RANC, Single Function Control of VAV with or without Optional Reheat
35E/J-A-3100: Single Duct Analog Control Sequence 3100: Temperature Responsive Control without Heat or with Hot Water Heat
35E/J-D-4240: BACnet Variable Air Volume Cooling Control Package No. 4240
35E/J-P-1105: Single Duct Pneumatic Control Sequence 1105: DANC, Multi-Function Control of VAV with or without Optional Reheat
35E/J-B-8270: BACnet VVT Bypass Damper Control Carrier Control Package No. 8270
35E/J-V-8220: VVT Damper Control, Pressure Dependent, Carrier Control Package No. 8200
35E/J-P-1104: Single Duct Pneumatic Control Sequence 1104: DANO, Multi-Function Control of VAV with or without Optional Reheat
35E/J-P-1102: Single Duct Pneumatic Control Sequence 1102: DANO, Single Function Control of VAV with or without Optional Reheat
35E/J-C-4150: ComfortID Variable Air Volume
35E/J-A-2100: Single Duct Analog Control Sequence 2100: Heating Control
35E/J-C-4140: ComfortID Variable Air Volume Cooling Control Package No. 4140
Application Data
35E,J Axis™ Single-Duct Terminal Units for Variable Air Volume Systems and Variable Volume/Variable Temperature (VVT) Systems
35L,N Dual Duct Terminal Units for Variable Air Volume Systems
Brochure
VVT Zoning System Brochure High Resolution 1/21
VVT Zoning System Brochure Print Version 1/21
A World of Comfort 2025 - Brochure (Printer Version)
Axis Overhead Air Terminals Brochure
VVT Zoning System Brochure Low Resolution 1/21
A World of Comfort 2025 - Brochure
Drawings
35J-202-3: Single Duct Terminal Units for Variable Volume Systems. 35JP Series, with Pneumatic Controls
35J-202-2: Single Duct Terminal Units for Variable Volume Systems. 35JA, JC, JV Series, with Electronic Controls
35J-202-1: Single Duct Terminal Units for Variable Volume Systems. Standard Series, No Controls
Guide Specifications
35J Guide Specifications, 45 to 3700 Nominal cfm
Product Data
35J Single-Duct Retrofit Terminal Units for Variable Volume Systems, 45 to 3700 cfm
i-Vu Open VVT Zone II Controller Product Data Sheet
i-Vu Open VAV Zone II Single Duct Product Data Sheet
Warranty Card
Warranty - Standard Product Warranty for Commercial Equipment
White Paper
Environmental Design Considerations for Hospital Operating Rooms White Paper
Intelligent Air Source and Terminal Integration
Wiring Diagrams
Single Duct Terminal Unit Control Package IVD0
4401_OPN-B3-P-02 Single Duct Cooling Only
Single Duct Terminal Unit Control Package SLJ5