TB & TM Series Thermostats

Technical Specifications

Features

Built-in temperature, humidity, and/or motion sensing for optimal control

Intuitive push-button interface with a clear LCD display

BACnet or MODBUS communication protocol capable (depending on model) for flexible system integration

Configurable inputs and outputs to support a variety of HVAC applications 

Real-time clock maintains accurate time for up to 7 days during power outages

Choice of 24VAC or 110-220V power supply for installation flexibility*

*Depending on thermostat model

Applications

Fan (FCUs): Enhance occupant comfort by providing individual control over fan speed and temperature

Rooftop Units (RTUs): Optimize RTU operation for energy efficiency through precise temperature and airflow control

Heat Pumps: Maximize heat pump performance and efficiency with integrated control of heating and cooling modes

Variable Frequency Drives (VFDs): Seamlessly integrate with VFDs to fine-tune motor speeds and optimize energy consumption

Specifications

TB Series (BACnet)
Options24 V, Temp. Only24 V, Temp, Humidity, Motion110-220V, Temp. Only
Branded Part #TB-24-CTB-24-HM-CTB-C
Unbranded Part #TB-24TB-24-HMTB
CommunicationBACnet MS/TP (subordinate device) | Baud rates up to 76.8 kbps, detected and set automatically by the thermostat
TM Series (Modbus)
Options24V, Temp., Humidity-110 - 220V, Temp. Only
Unbranded Part #TM-24-TM
CommunicationsModbus RTU (server) | Baud rates up to 76.8 kbps, detected and set automatically by the thermostat
Power Requirements24 VAC ± 15% 4VA no load, 76 VA Full Load110-220 VAC
DisplayLCD
SENSING ELEMENT
TemperatureRange: 41-95° (5-35°C), Accuracy: ± 1°F (0.5°C)
Humidity
Range: 10-90% Accuracy: ± 3% Typical
-X-
Motion
Sensor Type: PIR, quad, omnidirectional
Distance: 16.4 ft. (5 m)
Detection Range: 90 x 30 (HxV)
Movement Speed: 2.62 – 3.94 ft/s (0.8 – 1.2 m/s)
Detection Object: 15.75 x 9.84 in. (400 x 250 mm)
-X-
InputsT1, 0 - Normally Open (NO) or Normally Closed (NC) dry contract, or 0-10 Vdc AI, or 50 kOhm thermistor @ 77°F (25°C)
A, B - Communication +/- (RS485)
In1, 0 - NO or NC dry contract, or 0-10 Vdc AI, or 50 kOhm thermistor @ 77°F (25°C)
C, R – Power 24 VAC
Outputs11, 12, 13 – DO, 3A 14 – DO 0.3A 15, 16 - DO 0.3A or AO 0-10 Vdc, 5 mA max.,not isolated
Environmental Operating Range50° to 122°F (10° to 50°C), 10 - 90% RH, non-condensing
HousingSquare form factor, fire-retardant ABS plastic, UL94V-0
MountingInstalls to a standard wall box with mounting hardware included (consult technical instructions)
ComplianceFCC CFR47, chapter 1, subchapter A, part 15, class B
ICC, ICES-003, class B
CE Mark LVD, 2014/35/EU
RoHS 2011/65/EU
C-Tick Mark, AS/NZS 61000-6-3
CA Prop. 65

Documents

Installation

Carrier ComfortVu Tstat Stnd TB-TM Series Installation and Operation

Product Data

ComfortVu™ BACnet and Modbus Thermostats - Standard Models Product Data