TB & TM Plus Series Thermostats
Technical Specifications
Features
Easy-to-use touchscreen display
Temperature, humidity, and motion onboard sensors for optimal control
BACnet or MODBUS communication protocol capable (depending on model) for flexible system integration
Configurable inputs and outputs for versatile control
Real-time clock maintains accurate time for up to 7 days during power outages
Flexible power supply options (24VAC or 110-220V)*
*Depending on thermostat model
Applications
Fan (FCUs): Enhance occupant comfort by providing individual control over fan speed and temperature
Rooftop Units (RTUs): Optimize RTU operation for energy efficiency through precise temperature and airflow control
Heat Pumps: Maximize heat pump performance and efficiency with integrated control of heating and cooling modes
Variable Frequency Drives (VFDs): Seamlessly integrate with VFDs to fine-tune motor speeds and optimize energy consumption
Specifications
TB Plus Series (BACnet) | ||||
| Options | 24 V, Temp. Only | 24 V, Temp, Humidity, Motion | 110-220V, Temp. Only | - |
| Branded Part # | TBPL-24-H-C | TBPL-24-HM-C | TBPL-H-C | - |
| Unbranded Part # | TBPL-24-H | - | TBPL-H | - |
| Communication | BACnet MS/TP (subordinate device) | Baud rates up to 76.8 kbps, detected and set automatically by the thermostat | |||
TM Plus Series (Modbus) | ||||
| Options | 24V, Temp., Humidity | - | - | 110 - 220V, Temp, Humidity, Motion |
| Unbranded Part # | TMPL-24-H | - | - | TMPL-HM |
| Communications | Modbus RTU (server) | Baud rates up to 76.8 kbps, detected and set automatically by the thermostat | |||
| Power Requirements | 24 VAC ± 15% 4VA no load, 76 VA Full Load | 110-220 VAC | ||
| Display | Backlit, Resistive Touchscreen | |||
| SENSING ELEMENT | ||||
| Temperature | Range: 41-95° (5-35°C), Accuracy: ± 1°F (0.5°C) | |||
| Humidity Range: 10-90% Accuracy: ± 3% Typical | X | X | X | X |
| Motion | Sensor Type: PIR, quad, omnidirectional Distance: 16.4 ft. (5 m) Detection Range: 90 x 30 (HxV) Movement Speed: 2.62 – 3.94 ft/s (0.8 – 1.2 m/s) Detection Object: 15.75 x 9.84 in. (400 x 250 mm) | |||
| - | X | - | X | |
| Inputs | T1, 0 - Normally Open (NO) or Normally Closed (NC) dry contract, or 0-10 Vdc AI, or 50 kOhm thermistor @ 77°F (25°C) A, B - Communication +/- (RS485) In1, 0 - NO or NC dry contract, or 0-10 Vdc AI, or 50 kOhm thermistor @ 77°F (25°C) C, R – Power 24 VAC | |||
| Outputs | 11, 12, 13 – DO, 3A 14 – DO 0.3A 15, 16 - DO 0.3A or AO 0-10 Vdc, 5 mA max., not isolated | |||
| Environmental Operating Range | 50° to 122°F (10° to 50°C), 10 - 90% RH, non-condensing | |||
| Housing | Rectangular form factor, fire-retardant ABS plastic, UL94V-0 | |||
| Mounting | Installs to a standard wall box with mounting hardware included (consult technical instructions) | |||
| Compliance | FCC CFR47, chapter 1, subchapter A, part 15, class B ICC, ICES-003, class B CE Mark LVD, 2014/35/EU RoHS 2011/65/EU C-Tick Mark, AS/NZS 61000-6-3 CA Prop. 65 | |||
Documents
Installation
Carrier ComfortVu Tstat Plus TBPL-TMPL Series Installation and Operation
Product Data
ComfortVu™ BACnet and Modbus Thermostats - Plus Models Product Data