At a glance

Compressor Type

Cooling Only

Refrigerant

R-410A

Type

Condensing Unit

Capacity

6 - 20 Tons

Matched Air Handler(s)

40RUA, 40RUQ, 40RUS

Features

Performance Features
 

38AUZ single circuit cooling only System EERs from 11.5

ASHRAE 90.1 Efficiency Compliant

Standard crankcase heater

Compressor vibration isolation

Low ambient temperature control

Unit performance certified in accordance with ARI standard 340/360

 

Reliability Features
 

High and low-pressure switches

Anti-short cycling protection

Prepainted, galvanized steel cabinets that passes 500-hour salt-spray test

Compressor overload protection

Scroll compressor

E-Coat coil protection

UL, UL, Canada or ETL approved

 

Installation Features
 

Shipped with Puron (R-410A) refrigerant partial charge

Single-piece design

Perimeter base rail with forklift slots and lifting holes facilitates rigging

Suitable for mounting on the ground or the rooftop

24V control circuit transformer permits quick, easy wiring of thermostats

 

Maintenance Features
 

Comfort Alert™ diagnostic board

Powered and non-powered 115-v convenience outlet

Compressor access panel with easy grip handle

Easy starting, no-strip screw feature

Non-fused disconnect switch

 

Standard Limited Warranty
 

5 years parts only on compressor

One year parts only on all other parts

Options

Factory-Installed Options
 

E-Coat condenser coils for enhanced corrosion resistance

Non-fused disconnect switch for added safety

Powered convenience outlet for easy maintenance

Low ambient temperature Motormaster® control

 

Field-Installed Accessories
 

Programmed thermostats to enhance climate customization

Louvered hail guards for added coil protection

Additional Motormaster® controls for low-temperature regions

Physical Data

38AUZ/40RUA AHRI Cooling Ratings
 
UnitCooling StagesNominal Capacity
(tons)
Net Cooling Capacity
(MBH)
Total Power
(kW)
EERIEER
38AUZ07/40RUA0716716.211.512.2
38AUZ08/40RUA0817.5928.211.211.8
38AUZ12/40RUA1211011710.410.312.0
38AUZ14/40RUA14112.514813.511.012.0
38AUZ16/40RUA1621518416.411.213.2
38AUZ25/40RUA2522024021.811.011.2

 

AHRI = Air-Conditioning, Heating and Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
EER = Energy Efficiency Ratio
IEER = Integrated Energy Efficiency Ratio
COP = Coefficient of Performance

NOTES

  1. Rated in accordance with ARI Standard 340/360---07, as appropriate.
  2. Ratings are based on:
    • Cooling Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 35°C (95°F) db outdoor air temp.
    • IEER Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 4 various outdoor temperatures.
  3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.