Gemini® Split-System Heat Pump 38AUQ

Gemini® Split-System Heat Pump

Technical Specifications

At a glance

Compressor Type

3-Phase Heat Pump

Refrigerant

R-410A

Type

Condensing Unit

Capacity

6 - 20 Tons

Matched Air Handler(s)

40RUA, 40RUQ, 40RUS

Features

Performance Features
 

38AUQ Heat Pump EERs up to 11.0 and 3.5 COP

ASHRAE 90.1 Efficiency Compliant

Standard crankcase heater

Compressor vibration isolation

Low ambient temperature control

Unit performance certified in accordance with ARI standard 340/360

 

Reliability Features
 

High and low-pressure switches

Anti-short cycling protection

Prepainted, galvanized steel cabinets that passes 500-hour salt-spray test

Compressor overload protection

Scroll compressor

E-Coat coil protection

UL, UL, Canada or ETL approved

 

Installation Features
 

Shipped with Puron (R-410A) refrigerant partial charge

Single-piece design

Perimeter base rail with forklift slots and lifting holes facilitates rigging

Suitable for mounting on the ground or the rooftop

24V control circuit transformer permits quick, easy wiring of thermostats

 

Maintenance Features
 

Comfort Alert™ diagnostic board

Powered and non-powered 115-v convenience outlet

Compressor access panel with easy grip handle

Easy starting, no-strip screw feature

Non-fused disconnect switch

 

Standard Limited Warranty
 

5 years parts only on compressor

One year parts only on all other parts

    Options

    Factory-Installed Options
     

    Non-fused Disconnect

    Premium, E-coated condenser coil

    Convenience outlet (powered)

    Low ambient temperature Motormaster® control

    Louvered hail guards

     

    Field-Installed Accessories
     

    Low ambient temperature Motormaster® control

    Louvered hail guard

    Programmable thermostats

      Physical Data

      38AUQ/40RUQ AHRI Cooling Ratings
       
      UnitCooling StagesNominal Capacity
      (tons)
      Net Cooling Capacity
      (MBH)
      Total Power
      (kW)
      EERIEER
      38AUQ07 / 40RUQ071670.06.411.012.6
      38AUQ08 / 40RUQ0817.589.08.111.012.0
      38AUQ12 / 40RUQ12110112.010.211.012.0
      38AUQ16 / 40RUQ16215178.016.810.611.0
      38AUQ25 / 40RUQ25220220.020.810.711.0

       

      38AUQ/40RUQ AHRI High Heat Ratings at 47°F (8°C)
       
      UnitHeating StagesNominal Capacity
      (tons)
      Net Cooling Capacity
      (MBH)
      Total Power
      (kW)
      COP
      38AUQ07 / 40RUQ071666.05.93.30
      38AUQ08 / 40RUQ0817.587.07.73.30
      38AUQ12 / 40RUQ12110106.09.43.30
      38AUQ16 / 40RUQ16215178.015.33.40
      38AUQ25 / 40RUQ25220214.017.93.50
       
      38AUQ/40RUQ AHRI Low Heat Ratings at 17°F (-8°C)
       
      UnitHeating StagesNominal Capacity
      (tons)
      Net Cooling Capacity
      (MBH)
      Total Power
      (kW)
      COP
      38AUQ07 / 40RUQ071639.05.22.20
      38AUQ08 / 40RUQ0817.552.06.92.20
      38AUQ12 / 40RUQ1211070.09.32.20
      38AUQ16 / 40RUQ16215108.013.22.40
      38AUQ25 / 40RUQ25220130.015.92.40

       

       

       

      AHRI = Air-Conditioning, Heating and Refrigeration Institute
      ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
      EER = Energy Efficiency Ratio
      IEER = Integrated Energy Efficiency Ratio
      COP = Coefficient of Performance

      NOTES

      1. Rated in accordance with ARI Standard 340/360---07, as appropriate.
      2. Ratings are based on:  
        • Cooling Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 35°C (95°F) db outdoor air temp.  
        • IEER Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 4 various outdoor temperatures.
      3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.