TruVu™ UCXP I/O Expander
Technical Specifications
Features
Application Features
Comprehensive library of factory-engineered control programs available for complete air-side and water-side system control
Graphically programmable using the Snap programming tool
Hardware Features
Adds up to 4 outputs and 8 inputs (12 points total), to a TV-UCXP controller
Removable screw terminals for I/O connections
Supports din-rail or screw tab mounting
Hand-Auto-Off switches on all output channels
Software selectable configuration - no jumpers
Expanders can be mounted to TV-UCXP in a compact configuration or remotely mounted up to 1000 feet away
System Benefits
Fully plug-and-play with the Carrier i-Vu® building automation system
Supports demand limiting for maximum energy savings
Integrated Carrier linkage algorithm for plug-and-play integration with Carrier systems
Specifications
| Communication Ports | IO Bus port: Provides communication for wired TruVu UCXP I/O expander that is powered by an external power supply. |
| Inputs | 8 inputs • Inputs software configurable for 0-5 VDC, 0-10 VDC, 0-20 mA, thermistor, dry contact, or pulse counter. • Inputs are 16 bit A/D and support up to 40 pulses per second (12.5 msec min. pulse). |
| Outputs | 4 outputs • Outputs can be set as analog or binary outputs. • Analog outputs can be used for 0-10 VDC, 0-20 mA (12 bit A/D). • Binary outputs have a built-in relay and can be used to switch external devices or relays up to 1A, 30Vac/Vdc. |
| Protection | Two fast acting, 5mm x 20mm glass fuses: • A 2A fuse for the TV-UCXPIO expander’s power |
| Physical | Fire-retardant plastic ABS, UL94-5VA |
| Status Indicators | LED status of communications, power, running, errors, and outputs |
| Compliance | United States: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL listed to UL916, PAZX, Energy Management Equipment Canada: Industry Canada Compliant, ICES-003, Class A; cUL listed UL 916, PAZX and Energy Management Equipment Europe: EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment EN50491-3:2009, Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS) Low Voltage Directive: 2014/35/EU RoHS Compliant: 2011/65/EU Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3 |
| Environmental | -40 to 158ºF (-40 to 70ºC) 10 to 95% RH, non-condensing |
| Power Requirements | 24VAC ± 10%, 50-60Hz 50 VA power consumption 26VDC ± 10%, 12W |
Documents
Installation
TruVu IO Expanders (part no. TV-UCXPIO48)
Product Data
TruVu™ TV-UCXPIO48 Expander Product Data