TruVu™ UCXP I/O Expander TV-UCXPIO48

TruVu™ UCXP I/O Expander

Technical Specifications

Features

Application Features
 

Comprehensive library of factory-engineered control programs available for complete air-side and water-side system control

Graphically programmable using the Snap programming tool

 

Hardware Features
 

Adds up to 4 outputs and 8 inputs (12 points total), to a TV-UCXP controller

Removable screw terminals for I/O connections

Supports din-rail or screw tab mounting

Hand-Auto-Off switches on all output channels

Software selectable configuration - no jumpers

Expanders can be mounted to TV-UCXP in a compact configuration or remotely mounted up to 1000 feet away

 

System Benefits
 

Fully plug-and-play with the Carrier i-Vu® building automation system

Supports demand limiting for maximum energy savings

Integrated Carrier linkage algorithm for plug-and-play integration with Carrier systems

Specifications

Communication PortsIO Bus port: Provides communication for wired TruVu UCXP I/O expander that is powered by an external power supply.
Inputs8 inputs
• Inputs software configurable for 0-5 VDC, 0-10 VDC, 0-20 mA, thermistor, dry contact, or pulse counter.
• Inputs are 16 bit A/D and support up to 40 pulses per second (12.5 msec min. pulse).
Outputs4 outputs
• Outputs can be set as analog or binary outputs.
• Analog outputs can be used for 0-10 VDC, 0-20 mA (12 bit A/D).
• Binary outputs have a built-in relay and can be used to switch external devices or relays up to 1A, 30Vac/Vdc.
ProtectionTwo fast acting, 5mm x 20mm glass fuses:
• A 2A fuse for the TV-UCXPIO expander’s power
PhysicalFire-retardant plastic ABS, UL94-5VA
Status IndicatorsLED status of communications, power, running, errors, and outputs
ComplianceUnited States: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL listed to UL916, PAZX, Energy Management Equipment
Canada: Industry Canada Compliant, ICES-003, Class A; cUL listed UL 916, PAZX and Energy Management Equipment
Europe: EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment EN50491-3:2009, Part 3: Electrical safety requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS) Low Voltage Directive: 2014/35/EU RoHS Compliant: 2011/65/EU
Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3
Environmental-40 to 158ºF (-40 to 70ºC) 10 to 95% RH, non-condensing
Power Requirements24VAC ± 10%, 50-60Hz
50 VA power consumption
26VDC ± 10%, 12W

Documents

Installation

TruVu IO Expanders (part no. TV-UCXPIO48)

Product Data

TruVu™ TV-UCXPIO48 Expander Product Data

Need assistance? Ask Carrier.

Get in touch