TruVu™ Compact Link

Technical Specifications

Features

Link Features
 

BACnet Testing Laboratories (BTL) certified

Conforms to BACnet Router (B-RTR), and BACnet BBMD (B-BBMD) standard device profiles 

Supports BACnet routing between BACnet/IP, BACnet/Ethernet and BACnet/MSTP networks 

Can serve as the BACnet Broadcast Management Device (BBMD) 

Supports Modbus RTU and Modbus IP 

Supports up to 1,500 third-party BACnet points and up to 500 Modbus points (IP or Modbus RTU) 

Supports BACnet Foreign Device Registration (FDR) 

Supports SNAP graphical programs to create custom sequences

 

Hardware Features
 

IPv4 networks are supported 

Two 10/100 Mbps Ethernet Ports with fail-safe relay 

One isolated MS/TP Port, supporting speeds from 9.6 to 115.2 Kbps 

USB service port for local service: connect PC via a hard-wired connection or wirelessly using a USB-W adapter 

Compact footprint simplifies installation and optimizes panel space

 

System Benefits
 

Connects seamlessly to the i-Vu building automation system

Specifications

BACnet SupportConforms to the BACnet Building Controller (B-BC), BACnet Router (B-RTR), and BACnet Broadcast Management Device (B-BBMD) Standard Device Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision 15
Power Requirements24VAC ± 10%, 50-60Hz, 50 VA
24VDC ± 10%, 18W
Communication PortsMax Integration Points: Supports 1,500 BACnet points and 500 Modbus points (IP or Modbus RTU)
Eth0, Eth1: 10/100 BaseT, full duplex, Ethernet ports with built-in fail safe. Supports direct connection or daisy chain topology natively using BACnet/IP and/or BACnet Ethernet, or Modbus TCP/IP communication.
Port S1: For communication with a BACnet MS/TP network at 9600 to 115200 bps or with a Modbus serial network at 9600 to 115200 bps.
Port S2: For communication with a BACnet MS/TP network at 9600 to 115200 bps or with a Modbus serial network at 9600 to 115200 bps.
End of Net: Switch can be turned on to terminate the network segment.
Rnet: Supports up to 15 ZS sensors and one Equipment Touch or TruVu™ Equipment Touch.; Supplies 12 VDC/260 mA power to the Rnet across its rated temperature range.
Service Port: USB 2.0 host port for setting up the controller and troubleshooting through a local connection to a computer, connecting to the TruVu™ Equipment Touch, or the Carrier USB Wireless service adapter.
ProtectionDevice is protected by a replaceable, fast acting, 250 Vac, 3A, 5mm x 20mm glass fuse. The power and network ports comply with the EMC requirements EN50491-5-2
Real-Time ClockReal-time clock keeps track of time in the event of a power failure for up to 3 days.
LED Status IndicatorsTricolor NET LED to show network status / Tricolor SYS LED to show system status/POWER LED/S1 EON LED/A TX (Transmit) and RX (Receive)
LED for: Port S1 and Port S2
Environmental Operating Range40 to 158°F (-40 to 70°C), 10-95% relative humidity, non-condensing
The TV-CLB-E2 is suitable for installation inside or outside the building envelope. It should be placed in a UL Listed enclosure. If installed outside, the enclosure must be suitable for the environmental conditions.
ComplianceUnited States of America: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL Listed to UL 916, PAZX, Energy Management Equipment; 
Canada: Industry Canada Compliant, ICES-003, Class A cUL Listed UL 916, PAZX7, Energy Management Equipment; EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment RoHS Compliant: 2015/863/EU REACH Compliant; 
Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3
EnclosureFire-retardant plastic ABS, UL94-5VA
Mounting35mm DIN rail mounting or screw mounting

Documents

Installation

Modbus Integration Guide i-Vu® XT or TruVu controllers

BACnet Integration Guide i-Vu® XT or TruVu controllers

TruVu Compact Link BACnet Integrator (part no. TV-CLB-E2) Installation and Start-up Guide

N2 Open Integration Guide for TruVu controllers (drv_gen5)

KNX Integration Guide for TruVu controllers (drv_gen5)

SNMP Integration Guide for TruVu controllers (drv_gen5)

M-Bus Integration Guide for TruVu Controllers (drv_gen5)

TruVu Compact Link BACnet Integrator (part no. TV-CLB-E2) (drv_gen5) Installation and Start-up Guide

Modbus Integration Guide for TruVu controllers (drv_gen5)

Product Data

TruVu Compact Link Product Data Sheet

M Bus Protocol Product Data Sheet