TruVu™ Advanced Application Controller
Technical Specifications
Features
Application Features
Versatile controller suitable for a variety of applications, including: small AHUs, fan coils, exhaust fans
Standard library of control programs available for most unitary equipment and zone applications
Supports Carrier communicating sensors, which are available in a variety of zone and equipment sensing combinations
Supports Carrier TruVu touchscreen interfaces for managing and troubleshooting the connected equipment easily and for occupant engagement
Supports live, visual displays of control logic, which uses real time operational data and aids in optimizing and troubleshooting system operations
Supports SNAP graphical programs to create custom sequences
Hardware Features
Dual 10/100 Mbps IP ports
Supports home run, daisy chain and ring IP network topologies
Capacitor-backed real-time clock keeps time in the event of power failure or network interruption for at least three days
USB service port for local access: connect PC via a hard-wired connection or wirelessly using a USB-W adapter
DIN rail or screw mounting
System Features
Connects seamlessly to the i-Vu building automation system
Specifications
| BACnet Support | Conforms to the BACnet Building Controller (B-BC) and BACnet Broadcast Management Device (B-BBMD) Standard Device Profiles as defined in ANSI/ASHRAE Standard 135-2016 (BACnet) Annex L, Protocol Revision 15 |
| Power Requirements | 24 Vac ±15%, 50–60 Hz, 50 VA 24 Vdc ± 10%, 18 W |
| Max # of Control Programs | 2 |
| Communication Ports | Eth0,Eth1: 10/100 BaseT, full duplex, Ethernet ports with built-in fail safe. Supports direct connection or daisy chain topology natively using BACnet/IP and/or BACnet Ethernet communication. Rnet Port: Supports up to 10 ZS sensors, and one EQT1 or TruVu™ EQT3 Equipment Touch. Supplies 12/Vdc/260 mA power to the Rnet across its rated temperature range. Service Port: USB 2.0 host port for setting up the controller and troubleshooting through a local connection to a computer, connecting to the TruVu™ interface, or the Carrier wireless service adapter. |
| Inputs | 2 universal inputs electronically configurable in the control program for 0-5 Vdc, 0-10 Vdc, thermistor, dry contact or pulse counter. Resolution: 12 bit A/D Input Pulse Frequency: 10 pulses per second. Minimum pulse width (on or off time) required for each pulse is 50 msec. |
| Outputs | 2 analog outputs, 0-10 Vdc (10 mA max), PWM @ 80 HZ Resolution: 12 bit D/A |
| LED Status Indicators | Tricolor NET LED to show network status / Tricolor SYS LED to show controller status/POWER LED A TX (Transmit) and RX (Receive) activity LED and yellow link status LED for the following ports: Ethernet port Eth0 and Ethernet port Eth1/Output LEDs indicate status for each output/Prog LED is customizable |
| Compliance | United States of America: FCC CFR, Part 15, Class A; Canada: Industry Canada Compliant, ICES-003, Class A cUL Listed UL 916, PAZX7, Energy Management Equipment; Europe: Mark, UK: EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment RoHS Compliant: 2015/863/EU REACH Compliant |
| Real-Time Clock | Real-time clock keeps track of time in the event of a power failure for at least 3 days |
| Plastic Rating | Fire-retardant plastic ABS, UL94-5VA |
| Environmental | -40 to 158°F (-40 to 70°C), 10-95% relative humidity, non-condensing The TV-022-E2 is suitable for installation inside or outside the building envelope. It should be placed in a UL Listed enclosure. If installed outside, the enclosure must be suitable for the environmental conditions. |
Documents
Installation
BACnet Integration Guide i-Vu® XT or TruVu controllers
Ethernet Wiring for TruVu™ Dual IP Port Controllers
TruVu BACnet Advanced Application Controller (part no. TV-022-E2) Installation and Start-up Guide
Product Data
TruVu 022 Advanced Application Controller Product Data Sheet