i-Vu® UC Open XP IO
Technical Specifications
Features
Application Features
Comprehensive library of factory-engineered control programs available, including: Pump Control, Lighting Control, Time Scheduling with/without Override, Analog Temperature Control, Discrete & Permissive Interlock, Discrete Staging Control, OA Conditions, BTU Metering, Fuel Oil Metering, Electric Metering, Gas Metering, and Water Metering
Supports Snap graphical programming for creating customized control programs
Supports Carrier communicating room sensors, which allow for local setpoint adjustment and local overrides
Hardware Features
Expands the UC Open XP Controller to support up to 48 I/O points
Removable screw terminals for I/O connections
Versatile mounting options: may be mounted directly onto the UC Open XP enclosure or separately within the mounting enclosure
System Benefits
Integrated Carrier linkage algorithm for plug-and-play integration with Carrier systems
Fully plug-and-play with the Carrier i-Vu Building Automation System
Supports demand limiting for maximum energy savings
Specifications
| Communication Ports | Xnet Remote Expansion port: For connecting to a UC XP Controller via the Xnet network. |
| Inputs | 8 binary inputs: Inputs 1-8 are binary only and support pulse counting up to 10 Hz. 8 analog inputs: Inputs 9-16 are universal inputs, jumper selectable between thermistor/dry contact and 0-5VDC. All analog inputs have 10 bit A/D resolution. |
| Outputs | 8 binary outputs: Configured as dry contact, normally open, and must be powered from a Class 2 power source. |
| Protection | Incoming power and network connections are protected by non-replaceable internal solidstate polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events. |
| Status Indicators | LED status of power, outputs, running and errors. |
| Listed By | UL916 (Canadian Std. C22.2 No. 205-M 1983), CE, FCC Part15-Subpart B - Class A |
| Environmental Operating Range | Operating: -20° to 140°F (-29° to 60°C), 10-90% relative humidity, non-condensing Storage: -20°F to 140°F (-29° to 60°C), 10-90% relative humidity, non-condensing |
| Power Requirements | 24VAC +/- 10%, 50-60Hz 13VA power consumption 26VDC (25V min, 30V max) Single Class 2 source only, 100VA or less |
Documents
Brochure
VVT Zoning System Brochure Low Resolution 1/21
VVT Zoning System Brochure High Resolution 1/21
VVT Zoning System Brochure Print Version 1/21
Controls
i-Vu - Source Water Loop Control for UC Open XP Installation and Start-up Guide
Installation
UC Open XP/UC Open XP IO Installation and Startup Guide
Product Data
i-Vu Open UC Open XP IO Product Data Sheet
Warranty Card
Limited Warranty for i-Vu Control System and Field-Installed Open Controls