i-Vu® WSHP Water-to-Water Open Controller
Technical Specifications
Features
Application Features
Controls up to 4 stages of capacity (up to 3 compressor stages), to maintain the desired entering or leaving water temperature
Provides 5 operating modes for manual or automatic system changeover operation
Provides load water pump output control
Provides source water pump or 2-position isolation valve control
May be configured to reset the water temperature proportionally based upon OAT during cooling or heating modes
In cooling mode, the control has the capability to limit the OAT reset based upon the difference between a measured humidity value and a configured high RH setpoint limit
For larger installations, a total of up to 8 stages may be controlled as a singular heating or cooling source. One controller will operate as the master, coordinating others in the system
Hardware Features
Compatible with Aquazone™ water-to-water water source heat pumps with Puron® refrigerant
Integrates easily into any BAS using BACnet, Modbus, LonWorks or N2 protocols
On-board hardware clock, remote occupancy input, and support for communicating/thermistor sensors provide stand-alone operation
Easy startup and commissioning using i-Vu User Interfaces
System Benefits
Integrated Carrier Condenser Water Linkage algorithm for plug-and-play integration with the source water system when controlled by a Carrier water loop controller
Fully plug-and-play with the Carrier i-Vu Building Automation System
Supports demand limiting for maximum energy savings
Specifications
| BACNet Support | Advanced application controller (B-AAC), as defined in BACNet 135-2001 Annex L |
| Communication Ports | Network Comm port: EIA-485 port for BACnet MS/TP, Modbus RTU, or N2 communications (protocol and baud rate are DIP switch selectable); Comm Option port: For connecting a LON Option Card; Local Access port: For system start-up and troubleshooting (115.2 kbps); Rnet port: For connecting a T1 temperature sensor. |
| Inputs | 5 analog inputs: Leaving Load Water Temperature, Entering Load Water Temperature (optional), Leaving Source Water Temperature, Outdoor Air Temperature (optional) and Relative Humidity (optional). All AI’s have 10 bit A/D resolution. 5 binary inputs: Compressor 1 Status, Compressor 2 Status, Compressor 3 Status, Remote Occupancy Contact, and Safety Shutdown. |
| Outputs | 8 binary outputs: Stage 1 through Stage 4 Capacity Control, Reversing Valve, Source Water Pump/ Isolation Valve, Load Water Pump, and Alarm Lamp. Relay contacts rated at 3A max @ 24VAC, configured normally open |
| Protection | Incoming power and network connections are protected by non-replaceable internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events. |
| Real Time Clock | Battery-backed real time clock keeps track of time in event of power failure |
| Battery | 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of trend data & time retention during power outages. |
| Status Indicators | LED status indicators for communications, run status, error, power, and all digital outputs. |
| Controller Addressing | Rotary dip switches set BACnet MS/TP, Modbus, or N2 address of controller |
| Listed By | UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE EN50082-1997 |
| Environmental Operating Range | Operating: -40 to 158ºF (-40 to 70ºC), 10 to 95% RH, non-condensing Storage: -40 to 158ºF (-40 to 70ºC), 10 to 95% RH, non-condensing |
| Power Requirements | 24VAC +/- 10%, 50-60Hz, 14VA power consumption, 26VDC (25V min, 30V max), Single Class 2 source only, 100VA or less |
Documents
Controls
i-Vu - Source Water Loop Control for UC Open XP Installation and Start-up Guide
Installation
Water-to-Water Open Integration Guide v3
Water-to-Water Open Points/Properties v3
Product Data
i-Vu Open Water-to-Water Open Product Data Sheet