ZS Sensor Applications Guide
Remote Bank Sensor ZS-RMT-BNK
Sense temperature in harsh environments
Measure temperature in hard-to-reach areas, or location where a standard ZS sensor cannot be mounted
Make a standard thermistor sensor part of the Rnet network
Retrofit an existing thermistor sensor installation
Enable a wall button sensor when a standard ZS room sensor cannot be used
| Specification | Details |
| Enclosure Material | Polycarbonate, UL94V-0 |
| Enclosure Rating | NEMA 4, IP66, UV rated |
| Enclosure Dimensions | Width: 5 in. (12.7 cm) Height: 4.15 in. (10.54 cm) Depth: 2.5 in. (6.35 cm) |
| Remote Sensor | Thermistor 10K Type 2 (purchased separately), 22AWG twisted pair sensor cable, 50' max length |
| Power Requirements | 12 Vdc @ 6 mA |
| Power Supply | The 4-conductor Rnet cable from a controller supplies +12 Vdc @ 210 mA. For additional power, use an external power supply. Use the above power requirements to calculate the size of the external power supply. The controller and the external power supply must share a common ground. |
| Communication | 115 kbps |
| Mounting | 3/16 in. holes |
| Listed by | FCC Part 15-Subpart B-Class B, CE |
Application Guide
ZS Sensor Applications Guide
Installation
ZS Sensors Installation Guide
Product Data
ZS Remote Sensor Product Data Sheet