ZS Sensor Applications Guide
ZS Duct Sensors
| Sensing Element | |||
| Temperature | Range: 20° to 120°F (-5° to 50°C) Accuracy: ±0.36°F (0.2°C) | ||
| Humidity | Range: 10% to 90% Accuracy: Humidity is calibrated at 73°F (23°C) ±2.0% typical. Less than 0.5% drift per year. | ||
| Sensor | |||
| Temperature | Range: 20° to 120°F (-5° to 50°C) Accuracy: ±0.9°F (0.5°C) | ||
| Humidity | Range: 10% to 90% Accuracy: Humidity is calibrated at 73°F (23°C). ±2.0% typical. Less than 0.5% drift per year. | ||
| Enclosure Material | Polycarbonate, UL94V-0 | ||
| Enclosure Rating | NEMA 4, IP66, UV rated | ||
| Enclosure Dimensions | Width: 5 in. (12.7 cm) Height: 4.15 in. (10.54 cm) Depth: 2.5 in. (6.35 cm) | ||
| Probe | Temperature sensor probe: 304 SS / 0.25 in. (0.64 cm) diameter / Length (4 or 8 in.) specified at time of order Temperature/humidity sensor probe: ABS with SS filter / 1.0 in. (2.5 cm) diameter / 5.3 in. (13.5 cm) length Averaging temperature sensor probe: Bendable aluminum / 3/16 in. diameter / Length of 8, 12, or 24 ft. specified at time of order | ||
| Power Requirements | 12 Vdc @ 6 mA | ||
| Power Supply | The 4-conductor Rnet cable from a controller supplies +12 Vdc @ 210 mA. For additional power, use an external power supply. Use the above power requirements to calculate the size of the external power supply. The controller and the external power supply must share a common ground. | ||
| Communication | 115 kbps | ||
| Environmental operating range | -40 to 158°F (-40 to 70°C) | ||
| Mounting | Duct mount with #8 sheet metal screws | ||
| Listed by | FCC Part 15-Subpart B-Class B, CE | ||
Application Guide
ZS Sensor Applications Guide
Installation
Carrier Sensors Installation Guide
ZS Sensors Installation Guide
Product Data