WeatherExpert® Light Commercial Packaged High Outdoor Air System 50LCH

WeatherExpert® 50LCH Light Commercial Packaged High Outdoor Air System

Technical Specifications

At a glance

Type

Electric Heat/Cooling Only

Refrigerant

R-410A

Capacity Range

6 - 10 Tons

Efficiency (IEER)

20.8

Features

Performance Features
 

Exceeds ASHRAE 90.1 and Energy Star efficiency levels, as well as Consortium for Energy Efficiency (CEE) criteria

6, 7.5, and 10 ton nominal capacities with three-stage cooling capacity control

Up to 17.5 SEER and 20.8 IEER

6 to 10 ton models have standard cooling operation up to 125 °F (52°C) and down to 40°F (4°C)

EcoBlue™ vane axial supply fan with ECM motor provides up to 3” of external static capability at up to 350 CFM/ton

Modulating hot gas reheat for supply air temperature control with dehumidification

 

Maintenance Features
 

SmartVu control provides service reminders and alarming capability

Factory installed suction and discharge pressure sensors, readable from the SmartVu control interface

Hinged access panels on filter, control box, compressor, and supply fan motor compartments.

Innovative, easy starting, no-strip screw feature on remaining service panels

Two-inch disposable return air filters

Direct drive evaporator fan motor eliminates belt maintenance

Foil face insulation resists dirt entrapment and is wipe down capable

 

Installation Features
 

Field convertible from vertical to horizontal airflow (accessory kit required for size 08-10)

Provisions for thru-the-bottom power entry capability as standard

Single point electric, gas, and controls connections

Full perimeter base rail with built-in rigging adapters and fork truck slots

Factory installed OAT, OARH, RAT, RARH, and SARH sensor

Factory supplied, field installed SAT sensor

SmartVu control provides application and control flexibility

 

Reliability Features
 

Scroll compressors with internal line-break overload protection

24-volt control circuit protected with resettable circuit breaker

Permanently lubricated, direct drive supply fan motor

Totally enclosed condenser motors with permanently lubricated bearing

High-pressure switch protection

Refrigerant circuit pressure monitoring

 

Standard Limited Warranty
 

5 years parts only compressor

One year parts only on all other parts

Extended warranty packages available

Options

Factory-Installed Options
 

Medium or high electric heat with silicon rectifier control (SCR)

Return air or supply air smoke detector

Return air carbon dioxide (CO₂) sensor

High static direct drive supply fan motor

Duct pressure transducer for duct pressure control of supply fan speed

Building pressure transducer for zone pressure control of supply fan speed

Pre-coat or E-coat condenser or evaporator/HGRH coil

Louvered hail guards

Ultra low leak economizer with barometric relief

4” filter rack with MERV 8 or MERV 13 filters

Powered or non-powered convenience outlet

HACR circuit breaker or non-fused disconnect

Through the base electric & gas connections

Double wall construction with galvanized steel liner over R4 insulation

 

Field-Installed Accessories
 

Knockdown roof curbs

Modulating power exhaust

Supply duct cover for vertical to horizontal supply conversion (size 08-12)

Through the base electric & gas connections

4” filter rack with MERV 8 or MERV 13 filters

Louvered hail guards

Return air or supply air smoke detector

Horn/strobe annunciator and remote test/reset station for smoke detector

Return air carbon dioxide (CO₂) sensor

Physical Data

 

Nominal Cooling Ton SizeCooling StagesAHRI Efficiency SEER (EER)Dimensions (in) LxWxHElectric Heat Range
(kW)
6320.788 x 59 x 417.8-23.0
7.5319.9116 x 63 x 5712.0-30.3
10320.8116 x 63 x 5712.0-30.3

AHRI = Air-Conditioning, Heating & Refrigeration Institute
IEER = Integrated Energy Efficiency Ratio

NOTES

  1. Rated and certified under ARI Standard 210/240---06 or 340/360---07, as appropriate.
  2. Ratings are based on: 
    • Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor air temp and 95°F (35°C) db outdoor air temp.
  3. All 50LCH units comply with ASHRAE 90.1-2010 Energy Standard for minimum SEER and EER requirements..
  4. 50LCH units comply with US Energy Policy Act (2005).

Documents

Controls

50LC*H 07-12 WeatherExpert® Electric Cooling Packaged High Outdoor Air System with Puron® (R-410A) Refrigerant, Installation, Controls, and Start-up

Guide Specifications

50LC*H Guide Specifications, 6 to 10 Nominal Tons

Product Data

48/50LC*H 07-12 WeatherExpert® Packaged High Outdoor Air Systems, 6 to 10 Nominal Tons