Carrier® Comfort Network® Universal Controller 33UnivCtrl-01

Carrier® Comfort Network® Universal Controller

Technical Specifications

At a Glance

Application

Airside

Application

Packaged Indoor

Application

Packaged Outdoor

Application

Split Systems

Type

General Purpose Controller

Features

General
 

Integrates auxiliary building system control

Controls non-Carrier equipment and Carrier HVAC equipment not equipped with Product Integrated Controls, using the Carrier communicating network

Compatible with all standard Carrier network user interfaces

Stand-alone control and monitoring of up to 16 field points, using proven algorithms

Two LEDs, conveniently located on the front of the module, indicate processor status (red) and communication bus status (yellow)

Local connection for Carrier network

Total facilities management when linked to a Carrier network

Three-day backup of clock and data such as Runtime and Consumable

Batteries are not required

Uses any standard, field-supplied 24 vac, 60 va transformer

 

Functions
 

Constant Volume (CV) Cooling and Heating Control

Dehumidification

CV Mixed Air Damper Optimization

Fan Control

Pump Control

Lighting Control

Indoor Air Quality

Generic PID Control

Time Scheduling with/without Override

Analog Temperature Control

Discrete Interlock

Discrete Staging Control

Permissive Interlock

Nighttime Free Cooling

Set Point Reset

Optimal Start/Stop

Linkage to airside systems

Optimizes efficiency by fully integrating all HVAC operations

 

8 Inputs
 

Each input (1 to 8) can be used as a discrete, analog, or temperature input

Discrete inputs can be dry contact or pulsed dry contact

Analog inputs can be 4 to 20 mA or 0 to 10 vdc

Temperature inputs can be 5K or 10K ohm thermistors

 

8 Outputs
 

Each output (1 to 8) can be discrete or analog

Discrete outputs are 24 vdc at 80 mA

Analog outputs are 4 to 20 mA or 0 to 10 vdc (varies with point type)

 

Carrier Network Features
 

Alarm processing, messages, and annunciation

Runtime, history, and consumable data collection and report generation

Demand limiting

Broadcast of data such as outside-air temperature, outside air humidity, and time of day

Timed overrides for use with Tenant Billing

Airside linkage

 

Enclosure & Power Supply
 

Designed so that it can be easily installed in a field-supplied NEMA-1 enclosure

Uses any standard, Class II, SELVcompatible, field-supplied 24 vac, 60 va transformer