PremierLink™ Rooftop, Split-System and Heat Pump Controller
Application
Packaged Outdoor, Split Systems, WSHPsType
Product-Integrated ControllerFor RTUs & Split Systems | For Water Source Heat Pumps |
DCV ready with the use of the combination CO2 & temperature sensor Controls up to 3 stages of gas heat or combination of mechanical and electric heat to maintain space temperature set point Ability to control exhaust fan based on economizer or occupancy on 2-stage heat units Provides temperature compensated start of heating or cooling to achieve set point by the start of the scheduled occupied time PremierLink controller exists on the CCN network and is compatible with ComfortLink™ controller Integrated economizer control Unoccupied free cool if outdoor conditions are right Pre-occupancy purge for better IAQ Supports Navigator and Scrolling Marquee Display and alarms (v1.x only) Compatible with the T55, T56 , T58, T59 or the combination CO2 temperature sensor Dehumidification on units with factory installed HumidiMi$er Filter Switch input Auto Fan for occupied Input for remote Door Switch | Easy-to-use, cost effective DDC water source heat pump controller Used as part of a Carrier Comfort Network WSHP Installation Works with the 50RLP Aquazone System Control Panel to integrate a complete WSHP solution for coordinating, monitoring, and controlling the entire system Simple implementation with factory configured and installed controller, ordered as part of the model nomenclature for any Carrier WSHP product Can be supplied with 50RHC, RVC, RHR, RVR, RHS, RVS, RDS, HQ, VQ, KQ, RTG, and RWS products Ready-to-use PremierLink controller includes factory-installed sensors for easy installation Controls cooling and heating with a variety of CCN space temperature and IAQ sensors Monitors all safety functions to provide all the features outlined for the Complete C unit controls Provides the ability to relay safety alarms back through the network to a central computer Occupancy schedule and set point configuration capable Service configuration selection to customize service set points Control configuration selection to customize all control functions Monitors leaving air and water temperatures from the WSHP unit Includes supply fan status, remote time clock, and fire shut down input capabilities Can be used in conjunction with a Demand Control Ventilation system to provide a 0-20 ma signal to operate outdoor air dampers Can be used with Carrier Navigator, a portable display module that can be used to configure and perform service diagnostics at each unit (v 1.x only) Filter Switch input Auto Fan for occupied Input for high condensate switch |
| User Interface | The PremierLink™ controller is designed to allow a service person or building owner to configure and operate the unit through the CCN user interface. A user interface is not required for day-to-day operation. All maintenance, configuration, setup, and diagnostic information is available through the Level II communications port to allow data access by an attached computer running Network Service Tool, ComfortVIEW™, or ComfortWORKS® software. Data access also can be obtained from System Pilot™ or Touch Pilot™ devices. |
| Wiring Connections | Field wiring is 18 to 22 AWG (American Wire Gage). The PremierLink controller is a NEC (National Electrical Code) Class 2 rated device. |
| Inputs | Space temperature sensor Setpoint adjustment Outdoor air temperature sensor Indoor air quality sensor Outdoor air quality sensor/indoor humidity sensor Compressor lockout Fire shutdown Supply fan status Remote time clock/door switch Enthalpy status |
| Outputs | Economizer Fan Cooling stages 1 & 2 Heating stages 1 & 2 & 3 Exhaust/reversing valve/dehumidify/occupied |
| Power Supply | 2-wire, 24 VAC ± 15% at 40 va, 60 Hz |
| Power Consumption | Normal operating supply range is 18 to 32 VAC with minimum consumption of 10 VA |
| Hardware | Internal flash memory of 64K |
| Specified Sensing Temp Range | The PremierLink controller space temperature range is –40 to 245 F (–40 to 118 C). The PremierLink controller has an allowable control set point range from 40 to 90 F (4 to 32 C) for heating and 45 to 99 F (7 to 37 C) for cooling. |
| Communications | The number of PremierLink controllers is limited only by the maximum number of controllers allowed on a CCN system. Bus length may not exceed 4000 ft (1219 m), with no more than 60 devices on any 1000 ft (305 m) section. Optically isolated RS-485 repeaters are required every 1000 ft (305 m). Status and control data is transmitted at a baud rate of between 9600 and 38.4K. |
| Activity Indicators | Two activity indicators present on the PremierLink controller indicate activity. A green LED will indicate activity on the communication port and a red LED will indicate status of processor operation. |
| Environmental Ratings | Operating Temperature: –40 to 158 F (–40 to 70 C) at 10 to 95% RH (non-condensing) Storage Temperature: –40 to 185 F (–40 to 85 C) at 10 to 95% RH (non-condensing) |
| Vibration | Performance vibration: all planes/directions, 1.5G at 20 to 300 Hz |
| Shock | Operation: all planes/directions, 5G peak, 11 ms Storage: all planes/directions, 100G peak, 11 ms |
| Approvals & Compliance | Listed under UL 873, UL94-V0/5VB (plastic), and UL, Canada. CE Mark, ASHRAE 90 and ASHRAE 62-99 compliant. |