i-Vu® Open WSHP Controller

Technical Specifications

Features

Application Features
 

Controls 2 stages of DX cooling to maintain space temperature setpoint

Integrated 2-position or modulating waterside economizer for optimized mechanical cooling

Controls modulating or 2-position outside air damper to meet ASHRAE 90.1 requirements

Built-in advanced control routines for zone level humidity control or zone level demand control ventilation (ASHRAE 62)

Supports auxiliary modulating reheat, 2-position hot water/steam reheat, or electric heat

Independent fan speed and compressor staging ensures quiet operation and maximizes latent heat removal for increased occupant comfort

Modulating fan speed and compressor staging ensures safe unit operation

 

Hardware Features
 

Compatible with Aquazone™ horizontal and Puron® vertical water source heat pumps

Integrates easily into any BAS using BACnet, Modbus, or N2 protocols

On-board hardware clock, remote occupancy input, and support for SPT/thermistor sensors provide stand-alone operation

Easy startup and commissioning using Carrier’s BACview Handheld Service Tool

 

System Benefits
 

Integrated Carrier airside linkage algorithm for plug-and-play integration with the Carrier WSHP System

Fully plug-and-play with the Carrier i-Vu System

Supports demand limiting for maximum energy savings

Compatible with i-Vu Tenant Billing for tracking tenants’ after-hours energy usage

Specifications

BACNet SupportAdvanced application controller (B-AAC), as defined in BACNet 135-2001 Annex L
Communication PortsNetwork Comm port: EIA-485 port for BACnet MS/TP, Modbus RTU, or N2 communications
(protocol and baud rate are DIP switch selectable);
Comm Option port: For connecting a LON Option Card;
Local Access port: For system start-up and troubleshooting (115.2 kbps);
Rnet port: For connecting Carrier communicating room sensors and Carrier’s touchscreen user interface
Inputs4 analog inputs: Dedicated to Relative Humidity, Indoor Air Quality, Supply Air Temperature, and
Leaving Condenser Water Temperature. AI’s have 10 bit A/D resolution.
4 binary inputs: Stage 1 Compressor Status, Condensate Overflow, Fire/Smoke Detector, and
Fan Status (optional)
Outputs2 analog outputs: 1 dedicated to Outside Air Damper, and 1 configurable for either Auxiliary
Reheat or Waterside Economizer. AO’s have 10 bit D/A resolution.
8 binary outputs: Supply Fan
(low, medium, and high), Compressor Stage 1, Compressor Stage 2, Reversing Valve, Auxiliary
Heat/2-position Waterside Economizer, and Dehumidification. Relay contacts rated at 3A max @
24VAC, configured normally open
ProtectionIncoming power and network connections are protected by non-replaceable internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events.
Real Time ClockBattery-backed real time clock keeps track of time in event of power failure
Battery10-year Lithium CR2032 battery provides a minimum of 10,000 hours of trend data & time retention during power outages.
Status IndicatorsLED status indicators for communications, run status, error, power, and all digital outputs.
Controller AddressingRotary dip switches set BACnet MS/TP, Modbus, or N2 address of controller
Listed ByUL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE EN50082-1997
Environmental Operating RangeOperating: 0° to 140°F (-18° to 54°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing
Power Requirements24VAC +/- 10%, 50-60Hz
14VA power consumption
26VDC (25V min, 30V max)
Single Class 2 source only, 100VA or less