i-Vu® MPC Open XP IO
Technical Specifications
Features
Application Features
Comprehensive library of factory-engineered control programs available for complete air-side and waterside system control
Graphically programmable using the Snap programming tool
Supports Carrier communicating room sensors, which allow for local setpoint adjustment and local overrides
Hardware Features
Expands the UC Open XP Controller to support up to 96 I/O points
Removable screw terminals for I/O connections
First MPC XPIO expander can be mounted directly on MPC XP controller to save panel space
System Benefits
Compatible with i-Vu Tenant Billing for tracking tenants’ after-hours energy usage
Fully plug-and-play with the Carrier i-Vu Building Automation System
Supports demand limiting for maximum energy savings
Specifications
| Communication Ports | Xnet Remote Expansion port: For connecting to an MPC Open XP controller via the Xnet network. |
| Inputs | 8 inputs: Inputs are configurable for 0-5 VDC, 0-10 VDC, 0-20 mA, thermistor (10k Type II), 1k RTD (Platinum, Nickel or Balco), and Dry Contact. Inputs are 14 bit A/D and support up to 40 pulses per second (12.5 msec min. pulse). |
| Outputs | 4 outputs: Outputs jumper configurable for 0-10 VDC, 0-20 mA (12 bit A/D), or 24 VDC (50 mA relay drive). Outputs have HOA (hand/off/auto) switches, including potentiometer for manual adjustment of analog outputs. |
| Protection | Incoming power: 2 replaceable 3 AmpPico® fuses. The power, network, and I/O are also protected against voltage transient and surge events. |
| Status Indicators | LED status of power, outputs, running and errors. |
| Listed By | UL-916 (PAZX), cUL-916 (PAZX7)FCC Part 15-Subpart B- Class A, CE EN50082-1997 |
| Environmental Operating Range | Operating: 0° to 140°F (-18° to 60°C), 10-90% relative humidity, non-condensing Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing |
| Power Requirements | 24VAC +/- 10%, 50-60Hz 45VA power consumption 26VDC (25V min, 30V max) Single Class 2 source only, 100VA or less |
Documents
Installation
MPC Open XP, MPC XP IO48/816 Installation and Startup Guide
Product Data
i-Vu Open MPC Open XPIO Controller Product Data Sheet