Carrier 39DC Data Center Cooling: Air Handlers

Carrier 39DC Data Center Cooling System

Technical Specifications

At a glance

Construction

Double-Wall

Application

Indoor, Outdoor

Airflow Range

18,900 - 62,900

CFM (@25DT)

Features

Draw thru configuration

Direct drive airfoil blade fans with premium efficiency variable speed EC Motors

MERV 8 filters

Aluminum fin cooling coil 0020 copper tubes and 00075 aluminum fins

16 GA double wall construction  max leakage 1% at 6 WC pressure

Max deflection L/240

Single point piping connection

Custom color available (black is standard)

All service access from front of unit

Options

Seismic construction Ip10 or Ip15

Floor stand

Dual power connection with auto transfer switch

PLC based controls with pressure independent control valve

Blow thru configuration

Isolation damper

Plenum to connect unit to ceiling plenum

Software based teaming function

VFD with premium efficiency motors in lieu of ECM

Design for elevation up to 8000

Factory performance test at design conditions

Splits as required to fit existing space

Startup and first year warranty

Physical Data

 39DC-15039DC-25039DC-30039DC-500
Capacity150kW250kW300kW500kW
CFM @25DT18,90031,50037,70062,900
Approach6666
Fan kW69.714.924.6
Dimensions36”x96”x96”h48”x144”x102”h60”x168”x114”h60”x168”x168”h

Documents

Brochure

Carrier QuantumLeap Data Centers Solutions

Need assistance? Ask Carrier.

Find an expert