BACNet Support
|
Advanced application controller (B-AAC), as defined in BACNet 135-2001 Annex L |
Communication Ports
|
BACNet Port: EIA-485 port for BACnet MS/TP communications (9600 bps, 19.2 kbps, 38.4 kbps, and 76.8 kbps)
Local Access port: For system start-up and troubleshooting (115.2 kbps)
Rnet port: For connecting Carrier communicating room sensors and Carrier's touchscreen user interface |
Inputs
|
6 inputs: Configurable for thermistor or dry contact. Inputs 1 and 2 are also configurable for 0-5 VDC sensors. AIs have 12 bit A/D resolution. |
Outputs
|
5 binary outputs: Relay contacts rated at 1 A max @ 24 VAC/VDC, configured normally open. |
Protection
|
Incoming power and network connections are protected by non-replaceable internal solidstate polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, input, and output connections are also protected against voltage transient and surge events. |
Real Time Clock
|
Battery-backed real time clock keeps track of time in event of power failure. |
Battery
|
10-year Lithium CR2032 battery provides a minimum of 10,000 hours of trend data & time retention during power outages. |
Status Indicators
|
LED status indicators for communications, run status, error, and power. |
Controller Addressing
|
Rotary DIP switches set BACnet MS/TP MAC address of controller. |
Listed By
|
UL-916 (PAZX), cUL-916 (PAZX7)FCC Part 15-Subpart B- Class A, CE EN50082-1997 |
Environmental Operating Range
|
Operating: 0° to 140°F (-18° to 60°C), 10-90% relative humidity, non-condensing
Storage: -24°F to 140°F (-30° to 60°C), 10-90% relative humidity, non-condensing |
Power Requirements
|
24VAC +/- 10%, 50-60Hz
18VA power consumption
26VDC (25V min, 30V max
Single Class 2 source only, 100VA or less |
Dimensions
|
Length: 5-5/8” (14.3cm)
Width: 5-1/8” (13 cm)
Depth: 2” (5.1 cm)
Weight: 0.44 lbs. (0.20 kg) |