CCB/CCR

Semi-Hermetic
Compressor Pack Systems

Medium temperature application: 26 to 630 kW
Low temperature application: 9 to 212 kW

2 to 6 semi-hermetic Copeland STREAM 4 and 6 cylinders (4M and 6M)

  • Designed to be installed directly in technical room.
  • Application:
    • CC B : Low temperature R404A and R407F. Evaporating temperature -40°C to -25°C.
    • CC R : Medium temperature R404A, R134a and R407F. Evaporating temperature -15°C to -5°C.
    • CC H : High temperature R404A and R407F. Evaporating temperature -5°C to +5°C.
    • CC H : High temperature R134a. Evaporating temperature -10°C to +10°C.
  • Compressor pack system are designed for maximum operating pressures:
    • PS(LP)=17 bar and PS(HP)=28 bar for R404A/R407F
    • PS(LP)=15 bar and PS(HP)=19 bar for R134a.
  • Pack with total EC marked. Conform to PED 97/23/CE.